Dry Type Transformer

10 kV Class · 50–2500 kVA · IEC 60076-11

Transformer Equipment

Dry Type Transformer
10 kV Class · 50–2500 kVA · IEC 60076-11

Epoxy cast resin dry-type transformers for indoor, commercial and data center applications — IEC 60076-11 aligned.

Capacity
50–2500 kVA
Insulation
Class F (155°C) standard
Standard
IEC 60076-11
Cooling
AN / AF
Meet IEC design standards
Cross-reference & OEM available
Professional tech support
Project-verified supplier network
Product Description

Designed for practical power-asset applications

Cast-resin dry-type transformers for indoor distribution, commercial buildings and industrial installations. The final design is selected around voltage ratio, capacity, enclosure, cooling method, impedance and applicable approval requirements.

Supply & Documentation

What we confirm before quotation

We coordinate the technical and commercial details with the appropriate manufacturing partner before confirming price, lead time and documents.

Supply format

Project-configured equipment supplied through qualified manufacturing partners; rating, documentation and delivery schedule are confirmed before order acceptance.

Typical document package

Datasheet, dimensional or wiring information, inspection records and export documents are provided where applicable to the selected configuration.

Please include in your inquiry

  • kVA
  • Voltage
  • Certification requirements

Technical Specifications

StandardIEC 60076-11
TypeThree-phase epoxy cast resin dry-type
Rated Capacity50 – 2500 kVA (standard export range)
HV Voltage6, 6.6, 10, 10.5, 11 kV
LV Voltage0.4 kV (400 V); other LV on request
Vector GroupDyn11, Yyn0
Insulation ClassF (155°C) standard; H (180°C) optional
Temperature Rise100 K (F) / 115 K (H) at AN cooling
Impedance Voltage4% (≤160 kVA); 4–6% (200–630 kVA); 6% (800–1600 kVA); 6–8% (≥2000 kVA)
Partial Discharge≤ 10 pC typical at 1.5× Ur (factory test)
CoolingAN (air natural); AF upgrade ≈20–30% capacity boost
EnclosureIP20 standard; IP23 / IP54 optional
CertificationApproval documentation confirmed for the selected configuration

Parameters above reflect standard export configurations. Exact values for your voltage class, ratio or kVA rating are confirmed against the factory datasheet in the quotation before order acceptance.

Available Models

ModelSpecification
50–630 kVA10 kV class · impedance 4–6% · AN
800–1600 kVA10 kV class · impedance 6% · AN/AF
2000–2500 kVA10 kV class · impedance 6–8% · AN/AF

Exact ratings for your system voltage and duty are confirmed in the quotation against the factory datasheet. Custom configurations available on inquiry.

Features & Benefits

Cast-Resin Insulation

Epoxy cast-resin windings provide a clean, low-maintenance insulation system for indoor distribution service.

AN / AF Cooling

Natural-air cooling is standard; forced-air fan kits can be specified when the approved thermal design requires additional capacity.

Low Partial Discharge

Factory test criteria and resin processing are specified to support stable insulation performance over the transformer service life.

Project-Matched Enclosure

IP20, IP23 or higher enclosure options can be coordinated with the room layout, ventilation and touch-protection requirements.

Typical Applications

Commercial Buildings

Indoor power distribution for offices, hospitals, retail facilities and other occupied buildings.

Data Centres

Compact, low-maintenance transformer supply for critical power rooms, subject to the project short-circuit and redundancy design.

Industrial Plants

Plant distribution and motor-control power systems where indoor installation and reduced oil-related risk are preferred.

Renewable & Storage Sites

Auxiliary and collection-system distribution for solar, BESS and other energy projects with project-specific enclosure requirements.

Frequently Asked Questions

What information is needed for dry-type transformer selection?

Provide kVA rating, HV/LV voltage, frequency, vector group, impedance, cooling duty, enclosure rating, installation altitude and required standards.

Can the transformer be supplied with forced-air cooling?

Yes. AF cooling and the associated fan control arrangement can be specified when required by the approved thermal design.

Are CE or UL documents available?

Compliance documentation is confirmed for the selected design and destination market; UL-related requirements must be defined before quotation.